1. Overview
SPSW Series Smart Circuit Breakers (Smart Air Switches) can perform electrical measurements and remote control, targeting scenarios such as smart cities, industrial, and residential power distribution. On the basis of traditional circuit breakers, they integrate sensing, communication, control, and edge processing capabilities, enabling branch-level measurement, control, and management.
2. Product Parameters
| Item | Content |
|---|---|
| Example of Product Model | SYSWxxA / xP (xx = 32, 40, 63, 80, etc. specifications) |
| Overload current | 1–100 A (series coverage, subject to actual order) |
| Rated voltage | AC 220V, AC 380V |
| Under-voltage protection | About 160–200 V (range) |
| Over-voltage protection | About 240–260 V (range) |
| Leakage protection | 30 mA (typical value in brochure) |
| Frequency | 50 Hz |
| Breaking capacity | 10 kA |
| Power | < 1 W (brochure) |
| Pole example | 2P etc. |
| Communication Methods | NB-IoT, 2.4G WiFi, RS485, 4G, Ethernet (optional according to model) |
3. Performance Specifications
The following are laboratory-level indicators from the installation manual, which can be compared with the table above; environmental conditions in different sections may correspond to different test definitions.
| Item | Specification |
|---|---|
| Residual current detection / alarm range | 5~30 mA |
| Temperature measurement / alarm | Measurement 0℃~135℃; alarm 45℃~120℃ |
| Current measurement range | 16A / 20A / 32A / 63A / 80A / 100A (series) |
| Voltage measurement range | 100V~300V |
| Current / residual current accuracy | 0.2% |
| Temperature accuracy | 1℃ |
| Power Input | AC 220V ±20% |
| Power consumption | Full load about 1.5W; minimum about 0.5W |
| Wireless Communication Rate | About 20 kbps |
| Isolation Voltage | 2500 VAC |
| Operating / Storage Temperature and Humidity (§3.2) | Operating -10℃ to 70℃; Storage -50℃ to 80℃; humidity see manual |
4. Product Features and Functions
- Built-in residual current, temperature, current, and other sensors; 32-bit processor; supports JSON, MQTT, or LWM2M; 35mm rail mounting; Modbus-RTU/TCP.
- Measurement: temperature, voltage, current, power, power factor, frequency, residual current, four-quadrant energy; current harmonic measurement; optional local load "electrical fingerprint" identification.
- Protection: short circuit, leakage, overcurrent; over/under voltage, overload, electric arc (marketing materials); configurable thresholds and delays; optional hardware-level leakage protection.
- Control: Remote circuit breaker on/off; scheduled tasks (manual states up to 12 schedules); leakage self-test and automatic power-on (as shown in promotional materials).
- Communication: NB-IoT / 4G; RS485; Industrial Ethernet; PPT additionally lists WiFi (2.4G), etc., subject to actual sub-model.
5. AI Harmonic Analysis and Electrical Fingerprinting
Materials state that harmonic analysis can reach approximately 12,000 samples per second , measuring harmonics; using deep learning and sample analysis to establish an "electrical fingerprint" to identify load characteristics. Provides real-time "ECG-style" assessment for equipment and circuits, assisting in the recognition and warning of electrical safety features; can also perform harmonic analysis on front-end devices to determine equipment attributes and health status. Specific algorithms and indicators are subject to implemented firmware and cloud platform versions.
6. Cloud Platform and APP Capabilities
- Monitor user alarm information; centrally manage devices under the account; view electricity usage reports; view reports on power, voltage, etc.
- Support strategy configuration for device scheduling tasks, leakage self-check times, etc.
- Individual users can log in to the mobile app via phone number, WeChat, or QQ to perform remote settings, query, remote control, scheduled switching, leakage self-check, branch-level metering, and fault alarms (subject to the actual app).
- Collected measurements include: temperature, voltage, current, power (active/reactive/apparent), frequency, leakage, fault arcs, electricity consumption, harmonic current/voltage, etc., supporting energy statistics.
7. Open integration scenarios
Based on industrial Ethernet, 4G, NB-IoT, etc., integrate with smart buildings, smart energy, smart home, smart campus, smart hotels, smart communities, and electrical fire safety monitoring systems to achieve remote control, real-time alarms, statistical calculations, energy management, and big data analysis.
8. Appearance and Dimensions
| Type | Main Body Dimensions (Width × Depth × Height) |
|---|---|
| 2P Single Phase | 53 mm × 69.2 mm × 116 mm |
| 4P Three Phase | 89 mm × 69.2 mm × 116 mm |
9. Installation and Rated Input
Installation: 35mm standard rail; the usage environment should be free of explosion hazards, corrosive gases, and conductive dust, as well as protected against rain, snow, wind, sand, and static electricity.
Rated input (§4.7): AC 90–240 VAC, maximum 63A, 50/60 Hz.
Operating environment: Storage -40℃ to +85℃, Operation -25℃ to +65℃, Humidity 5%–90% RH (non-condensing).
10. Model coding
Model format: SPSW
| Rank | Meaning | Optional Values |
|---|---|---|
| ① Current Range | Rated Current | 16 / 30 / 63 / 80 / 100, etc. |
| ② Voltage Selection | Wiring Type | A: 1P; B: 2P (L+N); C: 4P Three-phase |
| ③ Communication | NB / 4G / RS485 | NB, 4G, RS |
| ④ Leakage | M Measurement only / N None / P Protection + Measurement | M, N, P |
| ⑤ Electrical fingerprint | N None / F Included | N, F |
Example: SPSW63-B-NB-MN; SPSW63-C-4G-PF
11. Terminals, Display, and Buttons
The panel includes Test, LED (Red/Green/Yellow), Reset, Safety Lock, Handle, etc.; NB/4G models include SMA antenna sockets. Refer to the diagrams in the manual for detailed terminal numbers.
The LED and Reset/Test work together to enter real-time view, Reset view, and sub-modes such as RS485/Wireless/Parameter Reset/Gateway Self-Configuration; the red light indicates an alarm. For specific operation and timing, see Chapter 5 of the manual.
- Must be installed and maintained by qualified personnel; power off and test for voltage before disassembly.
- Secondary circuit work of the current transformer must short-circuit the secondary winding to prevent an open circuit.
- Restore mechanical components and doors before powering on; violation may cause electric shock, fire, or explosion.